Sign In | Join Free | My ledscreensign.com |
|
Brand Name : Vertiv
Model Number : Vertiv GXT5 UPS
Certification : CE
Place of Origin : China
Payment Terms : T/T, Western Union, MoneyGram
Supply Ability : 1000pcs/months
Delivery Time : 60days
Packaging Details : cartons
Product name : Vertiv GXT5 UPS
Power level : 750VA - 3000VA
Technology : 230 VAC
Product type : Tower UPS/Rack-mounted UPS
Input Voltage : 230 VAC
Rated Frequency : 50 Hz / 60 Hz
Frequency Range : 40-70Hz; Auto Sensing
Output Voltage : 200/208/220/230/240 VAC
Rated frequency : 50-60Hz
Waveform : Sine wave
Battery Type : Valve-regulated,non-spillable, lead acid
Rated Voltage : 36 Vdc, 48 Vdc, 72 Vdc
Charger Current : Nominal 2.2 A; Maximum 8 A
Operating Temperature : Full power up to 40 ºC (up to 50 ºC with derating)
Storage Temperature, °C : - 15 to + 40
Relative Humidity : 0 to 95% non-condensing
Operating Elevation : Up to 3,000 m at 25°C without derating
Audible Noise : 46 dB
Safety : UL-1788 ,C-UL listed, IEC 62040-1 2 EN 62040-1
RFI/EMI : CISPR22 Class A (RFI) / FCC Part 15 (Class A)
Transportation : ISTA Procedure 1A
Vertiv Liebert GXT5-750IRT2UXL 750VA 750W Online Rack Tower UPS
The Liebert® GXT5™ UPS is a single phase, online double conversion UPS solution which offers premium power outage protection and continuous power conditioning in a compact and flexible deployment system. The new Liebert® GXT5™ from Vertiv™ is an advanced version of the widely-regarded GXT UPS Series. GXT5 is ideally suited to protect critical infrastructure in both centralized and edge network applications.
STANDARD SPECS
Ratings (VA /W). 750 VA / 750 W
Dimensions and Weight
Dimensions (mm) Unit, W×D×H 400×430×85
Unit Weight (kg) 16.5
Input
Rated Volatge 230 VAC
Rated Frequency 50 Hz / 60 Hz
Frequency Range 40 to 70 Hz
Power Factor ≥0.99
Input Power Cord C14
Output
Nominal Voltage 200/208/220/230/240 VAC
Waveform Sine wave
Inverter Overload Capability >200% minimum 250 ms, 150 to 200% for 2 seconds; 125 to 150% for 50 seconds; 105 to 125% for 60 seconds
Efficiency in Online Mode Up to 93%
Active Eco Mode Up to 98%
Output Receptacles (8) EN60320/C13
Internal Battery
Rated Voltage 36 Vdc
Charger Current Nominal 2.2 A; Maximum 8 A
Type Valve-regulated, non-spillable, lead acid
Qty x V x Rating 3 x 12 V x 9.0 Ah
End Cell Voltage 1.67 V/cell (discharge voltage per cell will be from 1.67 Vdc to 1.90 Vdc, canbe selected by PARAMSET)
Floating Voltage Equalize charge: 2.35 V/cell; Float charge: 2.27 V/cell
Battery Voltage Range 30 Vdc to 42.3 Vdc
General
Operating Temperature, °C Full power up to 40 oC (up to 50 oC with derating)
Storage Temperature, °C -20 to 60 ( contain batteries will be from -15 to 40 °C.)
Storage Temperature, °C -20 to 60 ( contain batteries will be from -15 to 40 °C.)
Relative Humidity 0 to 95% non-condensing
Operating Elevation Up to 3,000 m at 25°C without derating
Audible Noise <46 dBA max @ 3 ft. (1 m) front and sides <43 dBA max @ 3 ft. (1 m) rear
Safety UL-1778 (Fifth Edition), C-UL listed, IEC 62040-1: 2008 (First Edition) + Am 1:2013, EN 62040-1:2008+A1:2013
Transportation ISTA Procedure 1A
Surge Immunity : ANSI C62.41 Category B
![]() |
Vertiv Liebert GXT5-750IRT2UXL 750VA 750W Online Rack Tower UPS Images |